समाचार

Suction Accumulator, Function, Application Scenario & Capacity Selection

  • उनका वर्गीकरण:
  • दृश्य: ...
  • रिलीज का समय: 2026-10-31

Suction Accumulator, Function, Application Scenario & Capacity Selection

Suction accumulator is mounted on suction pipe before compressor; it intercepts liquid refrigerant and only lets gaseous refrigerant enter compressor. Liquid refrigerant entering compressor causes liquid slugging, washes away lubricating oil on cylinder wall, leading to rapid compressor damage. It is mandatory for blast freezer, hot gas defrost system and systems with large load fluctuation. Internal structure: baffle, oil return small hole; gas passes upward, liquid settles at bottom, oil slowly returns to compressor through tiny orifice. Xiteliduo blast freezer rack is equipped with suction accumulator as standard configuration. Medium temperature stable load cold room may omit accumulator if expansion valve superheat control is precise. Accumulator volume selection: match maximum possible liquid flood-back volume; too small cannot buffer liquid surge during defrost switching. Oil return hole blockage is common fault; oil accumulates inside tank, compressor oil level drops gradually. Accumulator outer surface frosting is normal under low temperature working condition; insulation can reduce heat absorption. Refrigeration maintenance & repair company checks oil return by monitoring compressor crankcase oil level before and after defrost cycle.

FAQ

  1. What is the core purpose of suction accumulator? Prevent liquid refrigerant from entering compressor.
  2. Which system must be equipped with suction accumulator? Blast freezer and hot gas defrost rack system.
  3. What disaster will liquid slugging cause? Cylinder lubricating oil washed out, compressor damage.
  4. How does oil return from accumulator? Through preset small oil return orifice at bottom.
  5. What fault if oil return hole blocked? Oil accumulates in accumulator, compressor oil shortage.
  6. Can stable medium temp cold room omit accumulator? Possible if superheat control is accurate.
  7. Is frosting on accumulator shell normal? Yes, it works under low suction temperature.
  8. What decides accumulator sizing? Maximum liquid flood-back volume during defrost switching.
इस लेख का वेबसाइट: https://hi.xtldcool.com/news/850.html

ऑनलाइन उत्पाद अनुकूलन योजनाएँ प्राप्त करें

कृपया नीचे दिए गए बॉक्स में आवश्यक जानकारी भरें, और आप इसे मुफ्त में प्राप्त कर सकेंगे।

परामर्श हेल्पलाइन

+86-18157593311

साइटेलिडुओ और चुआनली

R32 सेमी-हर्метиक पिस्टन कम्प्रेसर और कस्टम टर्नकी औद्योगिक रेफ्रिजरेशन सिस्टम के लिए चाइना सोर्स फैक्ट्री। स्व-विकसित कम्प्रेसर + पूर्ण रेफ्रिजरेशन समाधान, उष्णकटिबंधीय और अति-निम्न तापमान वाली कार्य स्थितियों के लिए स्थिर प्रदर्शन।

हमसे जुड़ें

तकनीकी सेवाएँ: +86-575-83665888;83068555 
कंप्रेसर हॉटलाइन: +86-18157593311 
इलेक्ट्रिक हीटिंग ट्यूब हॉटलाइन: +86-13857577938 
ईमेल:helenliu1983xtld@gmail.com
इलेक्ट्रिक हीटिंग ट्यूब फैक्ट्री: नंबर 150, डोंगहु गाँव, गानलिन टाउन, शेंगझोउ शहर, शाओक्सिंग शहर 
कंप्रेसर फैक्ट्री: नंबर 679, डोंगगुआ आर्थिक विकास क्षेत्र, शेंगझोउ शहर, शाओक्सिंग शहर

कॉपीराइट © 2026 झेजियांग ज़िटेलिडु एनवायरनमेंटल टेक्नोलॉजी कं., लिमिटेड और शेंगचुआनली एनवायरनमेंटल टेक्नोलॉजी कं., लिमिटेड। सर्वाधिकार सुरक्षित।