Every export cold storage piston refrigeration compressor must pass a full set of factory acceptance tests before packaging. Units failing any inspection item will be disassembled, adjusted and re-tested; defective products are not allowed to enter shipment warehouse.
Helium leak detection is used to inspect sealing performance of piston compressor. The test detects tiny leakage points with sensitivity up to 1×10⁻⁹ Pa·m³/s. This strict standard avoids refrigerant leakage during long sea transportation and later field operation.
24-hour full-load continuous running test is mandatory. During the test, technicians record exhaust pressure, oil temperature, motor current and vibration data every 30 minutes. All parameters must stay within design threshold without abnormal fluctuation.
Motor winding insulation resistance and high voltage withstand test verify electrical safety. The insulation resistance should exceed 200MΩ, and winding withstands specified high voltage without breakdown. This prevents motor short-circuit fault after shipment arrival.
For customized piston refrigeration compressor with anti-corrosion coating, salt spray test sample inspection is required. Coating sample undergoes 1000-hour salt spray test without rust spot formation, confirming suitability for coastal aquatic cold storage projects.
xtldcool piston refrigeration compressor factory keeps test records of each compressor unit. The test report is attached to shipping documents, helping overseas buyers and customs verify product quality and compliance during clearance.
Visual and dimensional inspection checks casing, crankshaft assembly, valve plate and piping interface. Dimensions deviation is controlled within 0.02mm for key moving parts. Non-compliant machining tolerance will accelerate wear of piston compressor during operation.
FAQ
Q: What leak detection method is used for export piston refrigeration compressor? A: Helium leak test is adopted to find micro refrigerant leakage points.
Q: How long is the mandatory full-load running test for piston compressor? A: Each finished unit undergoes 24-hour continuous full-load running test.
Q: What insulation resistance standard must piston compressor motor meet? A: Motor winding insulation resistance should be higher than 200MΩ.
Q: What salt spray test standard applies to anti-corrosion piston compressor? A: Coating sample passes 1000-hour salt spray test without rust spots.
Q: Will xtldcool provide factory test report with export shipment? A: Yes, unit test records and report are delivered together with goods.
Q: What tolerance control for key moving parts of piston compressor? A: Dimensional deviation of core components is controlled within 0.02mm.
Q: What data is recorded during full-load running test? A: Exhaust pressure, oil temperature, motor current and vibration are logged.
Keywords embedded: piston refrigeration compressor, cold storage piston compressor, piston refrigeration compressor factory, cold storage refrigeration compressor, semi-hermetic piston compressor, industrial piston refrigeration compressor, piston compression unit, piston refrigeration compressor OEM, piston refrigeration compressor export manufacturer, low-temperature cold storage piston compressor
Quality Inspection and Factory Test Items for Export Piston Refrigeration Compressor Before Shipment Complete factory testing for piston refrigeration compressor reduces hidden defects and cuts on-site failure risk for overseas cold storage projects.
Every export cold storage piston refrigeration compressor must pass a full set of factory acceptance tests before packaging. Units failing any inspection item will be disassembled, adjusted and re-tested; defective products are not allowed to enter shipment warehouse.
Helium leak detection is used to inspect sealing performance of piston compressor. The test detects tiny leakage points with sensitivity up to 1×10⁻⁹ Pa·m³/s. This strict standard avoids refrigerant leakage during long sea transportation and later field operation.
24-hour full-load continuous running test is mandatory. During the test, technicians record exhaust pressure, oil temperature, motor current and vibration data every 30 minutes. All parameters must stay within design threshold without abnormal fluctuation.
Motor winding insulation resistance and high voltage withstand test verify electrical safety. The insulation resistance should exceed 200MΩ, and winding withstands specified high voltage without breakdown. This prevents motor short-circuit fault after shipment arrival.
For customized piston refrigeration compressor with anti-corrosion coating, salt spray test sample inspection is required. Coating sample undergoes 1000-hour salt spray test without rust spot formation, confirming suitability for coastal aquatic cold storage projects.
xtldcool piston refrigeration compressor factory keeps test records of each compressor unit. The test report is attached to shipping documents, helping overseas buyers and customs verify product quality and compliance during clearance.
Visual and dimensional inspection checks casing, crankshaft assembly, valve plate and piping interface. Dimensions deviation is controlled within 0.02mm for key moving parts. Non-compliant machining tolerance will accelerate wear of piston compressor during operation.
FAQ
- Q: What leak detection method is used for export piston refrigeration compressor? A: Helium leak test is adopted to find micro refrigerant leakage points.
- Q: How long is the mandatory full-load running test for piston compressor? A: Each finished unit undergoes 24-hour continuous full-load running test.
- Q: What insulation resistance standard must piston compressor motor meet? A: Motor winding insulation resistance should be higher than 200MΩ.
- Q: What salt spray test standard applies to anti-corrosion piston compressor? A: Coating sample passes 1000-hour salt spray test without rust spots.
- Q: Will xtldcool provide factory test report with export shipment? A: Yes, unit test records and report are delivered together with goods.
- Q: What tolerance control for key moving parts of piston compressor? A: Dimensional deviation of core components is controlled within 0.02mm.
- Q: What data is recorded during full-load running test? A: Exhaust pressure, oil temperature, motor current and vibration are logged.
Keywords embedded: piston refrigeration compressor, cold storage piston compressor, piston refrigeration compressor factory, cold storage refrigeration compressor, semi-hermetic piston compressor, industrial piston refrigeration compressor, piston compression unit, piston refrigeration compressor OEM, piston refrigeration compressor export manufacturer, low-temperature cold storage piston compressor